4 mm shielded sensing; 10–32 VDC operating range; M12 connector; −40°C to 70°C operating.
Quick Engineering Summary
| Field | Value |
|---|---|
| Manufacturer | Omron |
| Category | Proximity Sensors - Industrial |
| Package | Cylinder, Threaded - M12 |
| Key electrical range | Operating Temperature: -40°C ~ 70°C; Output Type: NPN-NC/NO, 3-Wire; Response Frequency: 1kHz; Voltage - Supply: 10V ~ 32V |
Why is E2A-M12LS04-M1-C3 sustaining-only?
Discontinued status rules out a new design-in; keep this sensor only where an existing machine requires it. Secure parts for existing production and plan migration. EU RoHS compliance does not change that decision.
The wiring deserves attention before another unit goes onto a line. The catalog calls the output NPN-NC/NO and 3-wire, but Omron’s model legend and output circuit identify the -C3 variant as four-wire, with separate normally open and normally closed NPN outputs. Use the M12 pin arrangement on datasheet page 13 when maintaining the harness.
What does E2A-M12LS04-M1-C3's 4 mm range buy?
The 4 mm ±10% sensing distance applies to the specified ferrous target; Omron gives a 0 to 3.2 mm setting distance for the shielded M12 model. That setting range, rather than the nominal sensing distance, is the practical starting point for positioning a steel flag. Non-ferrous metal reduces sensing distance, but the datasheet’s material curves are typical, not guaranteed switch points.
Across −40°C to 70°C, temperature influence is specified as ±15% of the sensing distance at 23°C. Using the 4 mm nominal distance, 4 mm × 15 / 100 = 0.6 mm of influence relative to that reference. Do not treat that calculation as extra usable reach.
Where does E2A-M12LS04-M1-C3 lose electrical margin?
The 10 to 32 VDC operating range does not make the 200 mA maximum load current unconditional. At −40°C to −25°C with a 30 to 32 VDC supply, Omron limits load current to 100 mA: 200 mA − 100 mA = 100 mA less than the general ceiling. A load chosen against 200 mA alone can exceed the cold, high-supply limit.
At 200 mA with a 2 m cable, residual voltage is 2 V maximum. At a 10 V supply, 10 V − 2 V = at least 8 V across a load connected to the NPN output. Check the load’s required voltage at that condition; the 2 V figure is not an unloaded output specification.
What still needs checking for E2A-M12LS04-M1-C3?
The datasheet documents the connector pins and body dimensions, but does not give an explicit simultaneous-load limit for the NO and NC outputs. Resolve that limit before loading both channels near the stated 200 mA maximum. Its 1,000 Hz response frequency is an average measured with the standard target and prescribed spacing, not a guaranteed minimum pulse width for an arbitrary flag.
The page 18 drawing gives a 70 mm overall length and 56 mm body length; check rear clearance when retaining this long-barrel installation. For adjacent shielded M12 sensors, Omron specifies 20 mm side-by-side spacing. Crowding them can undermine detection even when each sensor fits its mounting hole.
View the Win-Source product page for E2A-M12LS04-M1-C3.
Key Takeaways for Engineers & Buyers
- Allow for 0.6 mm specified temperature influence relative to the 23°C sensing distance across −40°C to 70°C.
- At 10 V supply and 200 mA load with a 2 m cable, budget at least 8 V across the load.
- Reduce the 200 mA load ceiling by 100 mA when ambient is −40°C to −25°C and supply is 30–32 VDC.
How the figures on this page were worked out
| Result | Formula | Datasheet inputs | Value |
|---|---|---|---|
| Specified temperature influence against nominal sensing distance | Distance influence = nominal sensing distance × temperature influence percentage / 100 | Nominal sensing distance = 4 mm (Datasheet page 6, shielded M12 sensing distance); Temperature influence = 15 % (Datasheet page 6, ±15% of sensing distance at 23°C across −40°C to 70°C) | 0.6 mm |
| Minimum voltage across an NPN-connected load at low supply | Load voltage = supply voltage − maximum residual voltage | Supply voltage = 10 V (Datasheet page 6, lower end of operating voltage range); Maximum residual voltage = 2 V (Datasheet page 6, at 200 mA load current with 2 m cable) | 8 V |
| Reduction in load-current ceiling at cold ambient and high supply | Reduction = general load-current ceiling − conditional load-current ceiling | General load-current ceiling = 200 mA (Datasheet page 6, DC output load-current maximum); Conditional load-current ceiling = 100 mA (Datasheet page 6 note 2, at −40°C to −25°C ambient and 30 to 32 VDC supply) | 100 mA |