14mm sensing distance, M18 threaded body, 10V–30V supply, and -25°C to 70°C operating range.
Quick Engineering Summary
| Field | Value |
|---|---|
| Manufacturer | Omron |
| Category | Proximity Sensors - Industrial |
| Package | Cylinder, Threaded - M18 |
| Core function | SENSOR INDUCT 14MM NPN M18 NC |
| Key electrical range | Operating Temperature: -25°C ~ 70°C; Output Type: NPN-NC, 3-Wire; Response Frequency: 350Hz; Voltage - Supply: 10V ~ 30V |
A 14mm reach makes mounting the first decision
The mounting constraint is reach. With a listed 14mm sensing distance and an M18 threaded body, this shielded inductive sensor fits a fixed metal-target station only if the mounting position brings the target within reach; the number does not establish detection for every target geometry.
Omron E2E-X14C218-M1 is Active across the lifecycle fields, making new design-in reasonable once that fit is settled. EU RoHS compliance is stated. If the station needs more than the listed reach, it needs a different sensing arrangement.
350Hz sets the pace, not the pulse width
Fast-moving targets expose the weak point first. The 350Hz response-frequency ceiling bounds the stated switching rate, but it does not specify the shortest target passage the sensor will detect. A target that briefly enters the sensing zone can still produce a missed event.
IP67 and IP69K ingress ratings support use around wet machinery, though they do not establish protection for the assembled connector. The nickel-plated brass body and shielded construction describe the sensor being mounted; neither settles how the installed connection will hold up.
NPN-NC wiring and the 30V limit set the electrical fit
Even after the event-rate check, the control input remains. The listed 10V to 30V supply range brackets the rail choice: 30V is an upper limit, not permission to ignore rail excursions, while 10V is the lower boundary rather than a preferred setting. The NPN-NC, 3-Wire output needs an input arranged for that normally closed signal. A polarity mismatch can reverse what the controller reads as target present, so settle the logic before wiring rather than diagnosing a machine that reports the wrong state later.
The -25°C to 70°C operating range allows an ambient-temperature screen within those endpoints. It doesn't settle conditions at a hotter mounting point. Nor does the supply range establish how much load the output can drive; that question remains separate from choosing a rail within the stated limits.
Will the connector fit the existing harness?
Will this sensor mate with the installed harness? Box is the packaging designation, not a cable specification. Match the connector-terminated M18 sensor to the harness drawing before releasing E2E-X14C218-M1 for purchase.
The missing pinout holds up wiring release
Wiring release must wait. The datasheet still needs to supply the pinout and connector drawing before the harness can be fixed. The output load-current limit is absent, so the supply range alone cannot qualify the controller connection. Sensing-distance test conditions are absent too; 14mm does not establish detection against the actual target.
View the Win-Source product page for E2E-X14C218-M1.
Key Takeaways for Engineers & Buyers
- Check target geometry against the listed 14mm sensing distance.
- Compare the 350Hz response-frequency ceiling with the target event rate.
- Map the NPN-NC, 3-Wire output to the controller input before wiring.