15mm sensing distance, 10V ~ 30V supply limits, M30 body and -25°C ~ 70°C operating range.
Quick Engineering Summary
| Field | Value |
|---|---|
| Manufacturer | Omron |
| Category | Proximity Sensors - Industrial |
| Package | Cylinder, Threaded - M30 |
| Core function | SENSOR INDUCT 15MM PNP M30 NO |
| Key electrical range | Operating Temperature: -25°C ~ 70°C; Output Type: PNP-NO, 3-Wire; Response Frequency: 250Hz; Voltage - Supply: 10V ~ 30V |
A PNP-NO input is the first fit test
An NPN input won't work here. E2E-X15B1T30 5M has a PNP-NO, 3-wire output for an industrial inductive-sensing installation; the receiving controller must use that arrangement. Its M30 threaded cylinder fixes the mounting format, too.
Both lifecycle fields mark the part Active, making new design-in reasonable rather than a sustaining-only choice. EU RoHS compliance is listed.
The 15mm figure does not set the target gap
15mm is the listed sensing-distance ceiling, not the gap to set for every target. It helps with sensor placement, but the actual target still has to switch reliably at the intended position. The shielded construction matters when the M30 body sits in surrounding metal; no target-dependent sensing-distance detail is listed. Set the bracket position from the application target, not just the ceiling.
Supply and ambient limits decide whether the installation survives
The limits are firm. Check the machine rail against the listed 10V ~ 30V supply range: 30V is a ceiling, not a suggested setpoint, and a rail outside the range rules out the sensor before mounting begins.
The -25°C ~ 70°C operating range sets the installed sensor's ambient boundary. At 70°C, there is no basis for assuming a hotter enclosure will be acceptable. IP67 and IP69K are listed ingress ratings, but neither resolves how to route or seal the cable leads, and the receiving input still has to match the PNP-NO, 3-wire output. Otherwise, a correctly mounted sensor can remain invisible to the controller.
Cable leads make the harness the buying decision
The M30 mounting position constrains the cable route. Cable leads, not a plug-in connection, are the termination style, so confirm that the machine harness is built for them. Put termination and routing on the assembly instructions before fixing the bracket location; a sensor can fit that bracket and still delay the build if the lead arrangement does not fit. The LED indicator may help during installation, but it does not settle the connection.
The 250Hz figure needs switching context
250Hz is the listed response frequency. Without switching test conditions, that number cannot settle a fast-counting application. The wiring diagram, output load-current limit and mounting drawing are also absent; close those gaps before releasing the electrical connection and bracket.
View the Win-Source product page for E2E-X15B1T30 5M.
Key Takeaways for Engineers & Buyers
- Check the actual target and mounting against the listed 15mm sensing distance.
- Keep the sensor supply within the listed 10V ~ 30V limits.
- Plan the cable-lead termination before releasing the harness.